Permit Number: T03CM05689
Parcel: 115160330

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM05689
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/21/2004 JIM EGAN FIRE REVIEW Approved
01/21/2004 MVALDEZ1 PLUMBING-COMMERCIAL REVIEW Needs Review
01/21/2004 MVALDEZ1 WWM REVIEW Needs Review
01/21/2004 MVALDEZ1 MECHANICAL-COMMERCIAL REVIEW Needs Review
01/21/2004 MVALDEZ1 WATER REVIEW Needs Review
12/09/2003 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
12/09/2003 DAN CASTRO ZONING REVIEW Approved
12/09/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T03CM05689 DENIED 12/9/03
1. Provide overload protection for the new Walk-In Cooler per the Manufacturer's specifications, or demonstrate that the unit has this protection. Otherwise, provide a fuse at the dicsonnect sized at no greater than 125% of the nameplate rating of such equipment.
2. Connected VA for phase B is 6,800. Please correct from 6,150 and adjust total for this phase.
3. Line Diagram indicates a 50A CB on Panel A. If the highest phase is loaded to 81.75 amps, this breaker will not allow the load to operate.
4. Panel Schedule calls for a fuse on the panel. This is doubtful, especially since the line diagram indicates that the OCPD is a CB. Please clarify.
12/09/2003 JIM TATE ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/21/2004 MONICA VALDEZ OUT TO CUSTOMER Completed