Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T03CM05671
Parcel: 13355231A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM05671
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/03/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T03CM05671 DENIED 8/3/04
1. Minimum font size #10, which is a little over 1/8".
2. Provide Insta-hot disconnect per NEC 422 Part III, or justify otherwise. Typically, these units are not cord-connected.
3. Provide KVA for TV receptacle on Panel TF Ckt 20.
4. If RTU is existing, please indicate such. Note refers to Sheet M.1. There is no Sheet M.1 in this submittal.
5. It appears that the lights on Ckt TF-2 are (2) (3) (32) = 192 W, which is greater than 0.38 KVA.
6. It appears that the lights on Ckt TF-4 are (16) (3) (32) = 1536 W, which is greater than 1.20 KVA. Please clarify/correct as necessary.
7. Apply an additional 25% for all continuous loads on panel load calculations.
08/03/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the water pipe sizes to correspond to the provided calculations.
2. Revise the fixture unit calculations to correspond to the actual installed fixtures plus the proposed fixtures in the building.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/16/2004 BETH GRANT OUT TO CUSTOMER Completed