Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T03CM05671
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/03/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T03CM05671 DENIED 8/3/04 1. Minimum font size #10, which is a little over 1/8". 2. Provide Insta-hot disconnect per NEC 422 Part III, or justify otherwise. Typically, these units are not cord-connected. 3. Provide KVA for TV receptacle on Panel TF Ckt 20. 4. If RTU is existing, please indicate such. Note refers to Sheet M.1. There is no Sheet M.1 in this submittal. 5. It appears that the lights on Ckt TF-2 are (2) (3) (32) = 192 W, which is greater than 0.38 KVA. 6. It appears that the lights on Ckt TF-4 are (16) (3) (32) = 1536 W, which is greater than 1.20 KVA. Please clarify/correct as necessary. 7. Apply an additional 25% for all continuous loads on panel load calculations. |
| 08/03/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the water pipe sizes to correspond to the provided calculations. 2. Revise the fixture unit calculations to correspond to the actual installed fixtures plus the proposed fixtures in the building. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/16/2004 | BETH GRANT | OUT TO CUSTOMER | Completed |