Permit Number: T03CM05671
Parcel: 13355231A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM05671
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/22/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T03CM05671 DENIED 7/22/04

1. Provide lighting fixture schedule/cut sheet.
2. Provide power requirements for exhaust fan.
3. Document panel and circuit number for all new electrical loads.
5. All Insta-hot to electrical plans, with proper overcurrent protection and disconnect per NEC Article 422.
07/22/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide drawings sealed (and dated) by an Arizona Registrant.
2. Revise the water pipe sizes to correspond to the provided calculations. Note: The previous calculations show 4 GPM for a 1/2" pipe which is incorrect.
3. Revise the fixture unit calculations to correspond to the actual installed fixtures plus the proposed fixtures in the building.
07/22/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/03/2004 TAMI ACHONG OUT TO CUSTOMER Completed