Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T03CM05671
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/22/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T03CM05671 DENIED 7/22/04 1. Provide lighting fixture schedule/cut sheet. 2. Provide power requirements for exhaust fan. 3. Document panel and circuit number for all new electrical loads. 5. All Insta-hot to electrical plans, with proper overcurrent protection and disconnect per NEC Article 422. |
| 07/22/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide drawings sealed (and dated) by an Arizona Registrant. 2. Revise the water pipe sizes to correspond to the provided calculations. Note: The previous calculations show 4 GPM for a 1/2" pipe which is incorrect. 3. Revise the fixture unit calculations to correspond to the actual installed fixtures plus the proposed fixtures in the building. |
| 07/22/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/03/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |