Permit Number: T03CM05671
Parcel: 13355231A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM05671
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/28/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise restroom exhaust to conform to the site conditions.
04/28/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied
04/28/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise riser diagrams to coordinate with the floor plans.
2. Provide water pressure calculations to show how the piping has been sized. Show size and location of existing water line that is being tied into. Show that the existing line will not be overloaded by the additions of this project.
3. Provide vent for the floor drain.
4. Provide clean out for mop sink.
5. Provide upper terminal cleanout for drinking fountain.
6. Provide faucet for the lavatory that complies with ARS 45-313
06/02/2004 MELISSA POULIN WWM REVIEW Approved