Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T03CM05671
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/28/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise restroom exhaust to conform to the site conditions. |
04/28/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | |
04/28/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise riser diagrams to coordinate with the floor plans. 2. Provide water pressure calculations to show how the piping has been sized. Show size and location of existing water line that is being tied into. Show that the existing line will not be overloaded by the additions of this project. 3. Provide vent for the floor drain. 4. Provide clean out for mop sink. 5. Provide upper terminal cleanout for drinking fountain. 6. Provide faucet for the lavatory that complies with ARS 45-313 |
06/02/2004 | MELISSA POULIN | WWM | REVIEW | Approved |