Permit Number: T03CM05668
Parcel: 124090820

Address:
1722 E 9TH ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T03CM05668
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/09/2004 GERRY KOZIOL WWM REVIEW Denied Needs credit evaluation.
12/22/2003 David Witt BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T03CM05668


12/23/03 1722 E. 9TH ST.


PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ¼ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.
2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.


FOUNDATION PLANS:

1. NOTE ON THE DRAWINGS THE ALLOWABLE SOIL BEARING PRESSURE USED IN THE DESIGN OF THE FOOTINGS,
OR STATE THAT THE ASSUMED VALUE OF 1500 PSF IS BEING USED, PER TABLE R401.4.1, A SOILS REPORT IS
NOT REQUIRED. IT IS UP TO THE DESIGNER/HOMEBUILDER TO BE AWARE OF THE SOIL AND CONDITIONS OF
THE SITE. IF SOIL TESTING HAS BEEN DONE, A COPY OF THE SOILS REPORT SHALL BE SUBMITTED WITH THE
CONSTRUCTION PLANS, AND THE FOUNDATION DESIGN SHALL REFLECT THE SOILS REPORTS
RECOMMENDATIONS.

2. PLEASE DIMENSION THE DEPTH OF THE FOOTINGS BELOW NATURAL GRADE.

3. PLEASE REFERENCE FOOTINGS B and C TO THE FLOOR PLAN.

SECTIONS - DETAILS - MISC. NOTES:

1. PROVIDE A SPECIAL INSPECTOR FOR THE EPOXY.

2. B-B / 2 ; PROVIDE A CONNECTION FOR THE CURTAIN WALL / RAFTER.

3. B-B / 2 ; PROVIDE THE ROOF PITCH.

4. 5 / 2 ; THE DETAIL SPECS 2-2 X 12's AND THE FRAMING PLAN SPECS 3. I COULDN'T GET 2 TO WORK.

5. 7 / 2 ; PROVIDE ½" AIR SPACE AT THE SIDES, TOP, AND END OF THE BEAM. SEE R323 ITEM 4 .

6. 1 / 3 ; PLEASE SPECIFY THE LENGTH OF THE ANCHOR BOLTS.

7. 1, 2, 3, / 3 ; PLEASE SPEC THE ROOF / WALL CONNECTION. ALSO THE BEARING CONNECTIONS.

8. 3 / 3 ; THE VERTICAL #4's ARE REQUIRED TO BE GROUTED. GROUT CELLS ARE REQUIRED TO BE CLEANED OUT IF THE MORTAR PROJECTIONS EXCEED ½".

9. 4 / 3 ; PROVIDE A CONNECTION FOR THE PARAPET / ROOF.

10. THE #4's @ 48" ARE REQUIRED AND THE GROUT CELLS MAY NEED TO BE CLEANED OUT.

ELECTRICAL PLANS:

1. RECEPTACLE OUTLETS SHALL BE PROVIDED AT EACH KITCHEN COUNTER SPACE WIDER THAN 12", AND
SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24" FROM A RECEPTACLE
OUTLET, PER E3801.4.1 PLEASE CHECK THE SPACING AT EACH SIDE OF THE KITCHEN SINK.

2. PENINSULA COUNTER TOPS SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET AT EACH
COUNTER SPACE WITH A LONG DIMENSION OF 24" OR GREATER, AND A SHORT DIMENSION OF 12" OR
GREATER, PER E3801.4.2 AND E3802.4.3.

3. IS A TOP OR A PANTRY SOUTH OF THE REFRIDGERATOR? RECEPTACLE?

4. PLEASE SIZE THE CONDUCTORS TO THE GUEST HOUSE.

5. PLEASE SIZE THE CONDUCTORS TO SUB PANEL "B".



IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 791-5550 EXT. 1110

Final Status

Task End Date Reviewer's Name Type of Review Description
01/09/2004 CINDY AGUILAR OUT TO CUSTOMER Completed
01/09/2004 ANGIE SHOFFSTALL REJECT SHELF Completed