Permit Number: T03CM05643
Parcel: 133341220

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE ONLY

Permit Number - T03CM05643
Review Name: COMMERCIAL-BLDG/FIRE ONLY
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/06/2004 JIM EGAN FIRE REVIEW Approved
02/18/2004 Martin Haeberle BUILDING-COMMERCIAL REVIEW Denied 1. Table 1607.1 of the IBC requires the use of a 250 psf live load. Provide justification for utilization of an 85 psf live load by a published standard or revise plans and calculations to reflect the 250# load.
2. If the camber of the bridge is to be increased due to flood control/maintenance criteria the installation of handrails will be required complying with ANSI 117.1- 1998. Please clarify.
3. Please clarify if bridge is to be constructed in a fabrication facility. If so, provide third party certification of the facility.
02/19/2004 Laith Alshami ENGINEERING REVIEW Approved
02/25/2004 CAGUILA1 ELECTRICAL-COMMERCIAL REVIEW Needs Review