Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE ONLY
Permit Number - T03CM05643
Review Name: COMMERCIAL-BLDG/FIRE ONLY
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/06/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 02/18/2004 | Martin Haeberle | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Table 1607.1 of the IBC requires the use of a 250 psf live load. Provide justification for utilization of an 85 psf live load by a published standard or revise plans and calculations to reflect the 250# load. 2. If the camber of the bridge is to be increased due to flood control/maintenance criteria the installation of handrails will be required complying with ANSI 117.1- 1998. Please clarify. 3. Please clarify if bridge is to be constructed in a fabrication facility. If so, provide third party certification of the facility. |
| 02/19/2004 | Laith Alshami | ENGINEERING | REVIEW | Approved | |
| 02/25/2004 | CAGUILA1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |