12/23/2003 EROSE1 WWM REVIEW Needs Review
12/23/2003 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS
Sheet 2.0
1. Specify safety glazing for the 4020 window in the wall along the stairway. Ref. R308.4.9.

2. Notes at the first floor hall indicate stairs are to be constructed. Show the location of the stairs and handrail. Ref. R315.

Sheet 4.0
1. Show where toedown detail 4/4.0 occurs at covered porch and landings.

2. Show the minimum concrete footing width for two story conventional light frame construction. Ref. R403.1.




Sheet 6.0
1. Stair framing detail 2/6.0 shows riser dimensions that are not consistent with the plan callouts on Sheet 2.0. Coordinate plan dimensions with the detail.

PLUMBING COMMENTS - The plumbing portion has been reviewed and approved.

MECHANICAL COMMENTS
Sheet 8.0
1. Show path and termination of the kitchen exhaust hood. Ref. M1502.

ELECTRICAL COMMENTS
Sheet 9.0
1. The 40 amp water heater requires a #8 conductor. Ref. E3605.1.

ENERGY COMMENTS
Sheet 2
1. Note 14 states R-13 insulation is provided at exterior walls. Wall section 3/6.0 specifies R-19. Please clarify.