Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T03CM05614
Parcel: 123172510

Review Status: Completed

Review Details: 3RD PARTY REVIEW-RESIDENTIAL

Permit Number - T03CM05614
Review Name: 3RD PARTY REVIEW-RESIDENTIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/23/2003 EROSE1 WWM REVIEW Needs Review
12/23/2003 ELAINE ROSE ZONING REVIEW Needs Review
12/23/2003 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS
Sheet 2.0
1. Specify safety glazing for the 4020 window in the wall along the stairway. Ref. R308.4.9.

2. Notes at the first floor hall indicate stairs are to be constructed. Show the location of the stairs and handrail. Ref. R315.

Sheet 4.0
1. Show where toedown detail 4/4.0 occurs at covered porch and landings.

2. Show the minimum concrete footing width for two story conventional light frame construction. Ref. R403.1.




Sheet 6.0
1. Stair framing detail 2/6.0 shows riser dimensions that are not consistent with the plan callouts on Sheet 2.0. Coordinate plan dimensions with the detail.

PLUMBING COMMENTS
Sheet 7.0
1. HCS location is not consistent with the site plan. Coordinate the HCS location shown on the site plan with the plumbing drawings.

MECHANICAL COMMENTS
Sheet 8.0
1. Show path and termination of the kitchen exhaust hood. Ref. M1502.

ELECTRICAL COMMENTS
Sheet 9.0
1. Show the circuit number for the WP motion sensor.

2. The 40 amp water heater requires a #8 conductor. Ref. E3605.1.

ENERGY COMMENTS
Sheet 2
1. Note 14 states R-13 insulation is provided at exterior walls. Wall section 3/6.0 specifies R-19. Please clarify.
12/23/2003 EROSE1 NPPO REVIEW Needs Review
12/23/2003 EROSE1 ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/23/2003 ELAINE ROSE OUT TO CUSTOMER Completed