Permit Number: T03CM05608
Parcel: 12710017D

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM05608
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/03/2003 BLANCA ESPINO ENGINEERING REVIEW Approved
12/03/2003 MICHAEL ST. PAUL ZONING REVIEW Approved
12/04/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
12/04/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
12/04/2003 ROBERT SHERRY WATER REVIEW Approved
12/04/2003 JIM EGAN FIRE REVIEW Approved
12/04/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide calculations to show that adequate ventilation is being supplied to the new spaces. Reference Section 403.3, IMC 2000.
2. Show the air flow rates of the supply and exhaust for the new restrooms, Reference Section 403.2.1(3), IMC 2000.
12/05/2003 DROBEY1 BUILDING-COMMERCIAL REVIEW Needs Review
12/05/2003 GERRY KOZIOL WWM REVIEW Approved