Permit Number: T03CM05602
Parcel: 115072340

Address:
268 W ADAMS ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM05602
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/03/2003 JIM EGAN FIRE REVIEW Approved
12/03/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise hrizontal drain line from lavatory; it may not be connected to the vent of the water closet.
2. Show that the new water supplies to the new water closet and lavatory will not result in the existing piping being undersized. Reference Section 610.1, UPC 1994.
12/03/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
12/03/2003 ROBERT SHERRY WATER REVIEW Approved
12/03/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide information to show that the restroom exhaust flow exceeds the supply air. Reference Section 403.3, IMC 2000.
2. Show that the ventilation in the project area meet the requirements of Section 403.3, IMC 2000.
12/04/2003 MICHAEL ST. PAUL ZONING REVIEW Approved
12/09/2003 SREEVES1 WWM REVIEW Needs Review
12/09/2003 SREEVES1 BUILDING-COMMERCIAL REVIEW Needs Review
12/09/2003 SREEVES1 ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/09/2003 SUE REEVES OUT TO CUSTOMER Completed