Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T03CM05602
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/03/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
| 12/03/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise hrizontal drain line from lavatory; it may not be connected to the vent of the water closet. 2. Show that the new water supplies to the new water closet and lavatory will not result in the existing piping being undersized. Reference Section 610.1, UPC 1994. |
| 12/03/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/03/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/03/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide information to show that the restroom exhaust flow exceeds the supply air. Reference Section 403.3, IMC 2000. 2. Show that the ventilation in the project area meet the requirements of Section 403.3, IMC 2000. |
| 12/04/2003 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 12/09/2003 | SREEVES1 | WWM | REVIEW | Needs Review | |
| 12/09/2003 | SREEVES1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 12/09/2003 | SREEVES1 | ENGINEERING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/09/2003 | SUE REEVES | OUT TO CUSTOMER | Completed |