Permit Number: T03CM05601
Parcel: 129053900

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL

Permit Number - T03CM05601
Review Name: 3RD PARTY REVIEW-COMMERCIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/01/2004 TACHONG1 WWM REVIEW Needs Review
04/01/2004 TACHONG1 ENGINEERING REVIEW Needs Review
04/01/2004 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied Plans submitted for building permit have been checked for conformance with current codes. Corrections required are noted below. All corrections must be made to the original drawings and two new complete and corrected sets resubmitted along with a written reply to all comments. To facilitate a timely recheck please insure all drawing changes or revisions made to previously issued sheets are highlighted by cloud and revision number.

ARCHITECTURAL COMMENTS
Sheet 4
1. Provide a revised toilet room layout to allow the minimum fixture clearance requirements. Ref. ANSI A117.1 604.2. See attached sketch.

2. Provide a note on the plan that quantities of hazardous materials in use and in storage will comply with IBC 307.7. Note that there will be no welding in the building.

STRUCTURAL COMMENTS
1. Keynote 9 specifies 5/8’ OSB roof material. Roof diaphragm notes specify ½” OSB. Please resolve discrepancy. Comment restated.

PLUMBING COMMENTS
Sheet 1
1. Dimension a minimum horizontal distance between the HCS and water supply lines. Ref. UPC 609. Comment restated.


MECHANICAL COMMENTS- The mechanical portion has been reviewed and approved.

ELECTRICAL COMMENTS
Sheet 5
1. Revise the water heater height dimension to 84” to match the plumbing plan.

2. The site utility plan shows an overhead electric drop to the service. Revise the one line diagram to reflect the construction requirements. Comment restated.

ENERGY COMMENTS – The energy portion has been reviewed and approved.

Should you have any inquires regarding this letter, please do not hesitate to contact the Plans Examiner at (520) 791-2007 or the Building Official at (520) 791-5550.
04/01/2004 TACHONG1 ZONING REVIEW Needs Review
04/01/2004 TACHONG1 WATER REVIEW Needs Review
04/01/2004 TACHONG1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/01/2004 TAMI ACHONG OUT TO CUSTOMER Completed