Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T03CM05590
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/24/2004 | Robert Sherry | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed, show sizes on the drawings. Provide sizes for the roof scuppers. Reference Section 103.2.3, UPC 1994. 2. Comment not addressed, show sizes on the drawings. Provide overflow drains that are independent from the roof scuppers. Reference Section D1.1 (d), UPC 1994. 3. Revise the water pressure calculations to include the pressure drop due to the reduced pressure backflow preventer. Reference Section 610.2, UPC 1994. 4. Resize the RPBP to comply to Section 610.2, UPC 1994. 5. Resize the water meter to reduce the excessive pressure drop. Reference Section 610.2, UPC 1994. 6. Resize the water piping based on the provided schedule of water fixture units and the revised water pressure calculations. Reference Sections 610.3, UPC 1994. 7. The information provided for the hub drain (HD-1) does not show compliance with Section 410.1, UPC 1994. Section 410.1 requires a flange for a watertight joint with the floor. 8. Provide an approved, listed, pressure relief valve for the "expansion tank relief discharge" pipe (detail 1/P3.1). 9. Provide the listing for the Hydroment Ultraset Elastomeric Waterproof Membrane (detail 9/P3.1) that shows the material is suitable for coating a concrete basin for use as a mop sink. Reference Section 410.0, UPC 1994 and IAPMO Installation Standard IS 2-90. |
| 03/24/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the submitted structural calculations for hood support to comply with the requirements of Section 507.6, IMC 2000. 2. Revise Detail 19/M4 to comply with Section 506.3.11, IMC 2000. The minimum separation between a grease duct and its enclosing shaft is 6", not 3" (see also detail 8/A2.1). |
| 04/08/2004 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 04/12/2004 | Linda Buczynski | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 04/14/2004 | Martin Haeberle | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Provide structural calculations for the Cupola tower. Note: in order to defer this item approval of the Building Official is required. Provide a letter to Dave Mann, P.E. for approval. Please include approximate time of submittal. |
| 04/27/2004 | DAVID RIVERA | ZONING | REVIEW | Denied | Zoning will review and approve the building plans once the structural and commercial reviewers have approved the building plans. Also, a site card with DSD approvals by Fire, Zoning, Handi-cap, Engineering, and Landscape/NPPO is required before approval of the building plan. Copies of the approved development plan have been included with the building plan packet but have not been processed through the site plan approval. No fees are involved in re-stamping the development plan as an approved site plan. The development plan may be walked through for stamps and site card sign off. Copies of the stamped development plan, landscape and NPPO plans must be processed together. |