Permit Number: T03CM05590
Parcel: 11520005K

Address:
1905 W GRANT RD

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T03CM05590
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2004 Martin Haeberle BUILDING-COMMERCIAL REVIEW Denied 1. Indicate on plans that the shop drawings for the awnings and trusses, including calculations, shall be submitted and approved prior to installation.
2. Provide structural calculations for method of attachment of kitchen hood to the trusses.
3. Provide structural calculations for the Cupola tower.
4. Sheet DP-1 to be signed and dated by the registrant.
5. An occupant load sign is required in dining area. Show location on plans. Reference section 1003.2.2.5 IBC
6. Indicate premises identification per Pima County addressing ordinance.
7. Toilet room doors shall not swing into the clear floor or ground space for any fixture. Revise plans. References section 603.2.3 ANSI A117.1
12/11/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide sizes for the roof scuppers. Reference Section 103.2.3, UPC 1994.
2. Provide overflow drains that are independent from the roof scuppers. Reference Section D1.1 (d), UPC 1994.
3. The site drawing (DP-1) shows the size of both the water meter and the reduced pressure backflow preventer assembly as 1" with a 1-1/4" supply pipe but drawing P3 calls for a 1-1/2" supply pipe and a ¾" meter. Please coordinate the drawings and insure that the reduced pressure backflow preventer complies with Section 610.2, UPC 1994.
4. Provide a schedule of water and waste fixture units for all plumbing fixtures, including all of the kitchen equipment connected to the plumbing system, using the values shown in Tables 6-3 and 7-3, UPC 1994. Include the total number of each fixture being installed. Resize water piping as required. Reference Sections 610.3 and 703.1, UPC 1994.
5. Provide information to show that the hub drain (HD-1) complies with Section 410.1, UPC 1994.
6. Clarify the reason for an "expansion tank relief discharge" pipe (detail 1/P3.1).
7. The specified expansion tank, ET-1, is not listed for potable water use. Reference Section 301.1.1, UPC 1994.
8. Coordinate the gas demand values shown on the gas isometric with the gas demand values shown on the gas demand schedule. Correct the arithmetic on the demand shown for the branch serving the kitchen hood.
9. Correct the size of the connection to the dual fryer to correspond to the pipe capacities shown in Table 12-3, 1994 UPC.
10. A double check valve is not acceptable for protecting the water supply to a carbonator. Reference Section 603.3.12, UPC 1994 with AZ State amendments.
11. Appliances to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps may require reduced pressure principle backflow preventers. Please submit equipment sheets for determination. Reference Section 603.0, UPC 1994.
12. Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (drain lines serving sinks and urinals require cleanouts regardless of length). Reference Section 707.4, UPC 1994.
13. Clarify waste line connection for floor sink (FS-1) located under Packline Station (426); is it connected to the grease waste (P2) or the sanitary waste (P2.1)? Reference Section 1008.2, UPC 1994.
14. Clarify waste line connection for the hand sink (S-1) located on the east wall and the floor drain (FD-1) located east of the Fry Station Add-on (406); are they connected to the grease waste or the sanitary waste? Reference Section 1008.2, UPC 1994.
15. Provide calculations used to size the grease interceptor. Provide listing information for the grease interceptor. Reference Sections 301.1.1 and H4 (b), UPC 1994.
16. Provide protection of the trap seals for all floor drains. Reference Sections 1007.0 and 1007.1, UPC 1994, as amended by the State of Arizona.
17. Floor drain FD-1 is not an approved receptor for indirect waste. Reference Section 804.1, UPC 1994.
12/11/2003 Robert Sherry MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide integrated economizer with each rooftop A/C unit or increase minimum unit efficiency as shown in Table 703.6, IECC 1998. Reference Section 703.6, IECC 1998.
2. Coordinate the outside air requirements shown on the HVAC Schedule with the OA Compliance Schedule. Reference Section 106.3.1, IMC 2000.
3. The makeup air required for the kitchen hood appears to depend on the outside air that is provided by RTU-2 and RTU-3 to comply with Section 508.1, IMC 2000. Provide electrical interlocks for RTU-2 and RTU-3 to insure that adequate makeup air is provided whenever the kitchen hood is in operation.
4. Provide structural calculations to verify hood support and rod attachment (Detail 17/M4) complies with Section 507.6, IMC 2000.
5. Revise Detail 19/M4 to comply with Section 506.3.11, IMC 2000.
12/11/2003 ROBERT SHERRY WATER REVIEW Approved
12/15/2003 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT LBUCZYN1@CI.TUCSON.AZ.US
IF YOU CARE TO DISCUSS.

Sheet E2
1. Delete the Service Entrance Equipment Elevation (East Coast Section), as it contains redundant information which is not in all cases even Code-compliant, such as #10 conductor protected by 60A CB.
2. Change the title "Grounding Notes" to reflect the actual content. Notes look good and should remain.
3. On the line diagram, check references to NEC 250- 79c, 250-80a, and 250-81 a-d. No such Code sections.
4. On the load calculations (labeled "Single Line Diagram"), Panel D 48,954 VA was transcribed as 43, 954. Also please note that the 65% demand factor is permissible for services as well as feeders, and that the lighting should have been taken at 125%. This being said, the load summary result is smaller than is indicated, but it is probably best to correct this for a new facility.

Sheet E2.1
1. Please correct wire size on CKTS C-6 and C-8 to #10, per Keynote 12 on Sheet E3.
2. CB on CKT H-2,4,6 should be 35A per NEC 240-6 and 422-11(e) (3), unless the 40A is indicated on the appliance. Please correct as necessary.

Sheet E3
1. Show disconnect for Refrigerator Equipment 40 per NEC 422.
2. Hot Water System Equipment 44 is protected by a 40A CB on A-21,23, but is 50 A on equipment schedule. Please coordinate and clarify.

Sheet E4
1. 1998 IECC does not make exception for decorative lighting, and the W/SF is 1.97, which exceeds 1.7. Suggest that some of the "decorative" lighting be selectively toned down such that the overall theme of the restaurant is achieved with a minimum of power consumed for decorative purposes.
2. Please provide cutsheets for lighting fixture "B". Will be looking for full cut-off lighting distribution.

Sheet E8
1. Detail 1 Keynote 3 indicates a duplex outlet, but points to a telephone outlet. Please clarify.
2. Detail 1 Keynote 2 is "Not Used", but points to a telephone outlet. Please clarify.
12/24/2003 PATRICIA GEHLEN ZONING REVIEW Denied Zoning
12/24/2003
Building plans may not be reviewed until the approved development and landscape plans are included in each set of the submittal plan.
12/24/2003 JIM EGAN FIRE REVIEW Approved
12/29/2003 GERRY KOZIOL WWM REVIEW Denied Needs Wastewater 8th floor review of private sewer easement crossing property @ 1893 W Grant Rd.
12/30/2003 LOREN MAKUS ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/07/2004 TAMI ACHONG OUT TO CUSTOMER Completed
01/07/2004 ANGIE SHOFFSTALL REJECT SHELF Completed