Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T03CM05578
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/16/2004 | MELISSA POULIN | WWM | REVIEW | Approved | |
| 01/16/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/02/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
| 12/02/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/02/2003 | DAN CASTRO | ZONING | REVIEW | Approved | |
| 12/11/2003 | JIM TATE | ENGINEERING | REVIEW | Approved | |
| 12/23/2003 | NEAL SAUNDERS | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 12/23/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T03CM05578 DENIED 12/11/03 1. Max. fuse size 45AF on Sheet M1. Coordinate & clarify. 2. Load calculations total to 333 > 279. Please re-check, and correct as necessary. 3. Provide available fault current at New Panel A. 4. Show fault current rating at New Panel A. |
| 12/23/2003 | NEAL SAUNDERS | MECHANICAL-COMMERCIAL | REVIEW | Approved |