| 12/23/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T03CM05577 DENIED 12/11/03 1. Provide a disconnect for the Insta-Hot per NEC 422 Part C. 2. Load calculations total 333 > 279. Please re-check and correct as necessary. 3. Show available fault current at new location of Panel B, and rating of panel. |