Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T03CM05577
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/16/2004 | MELISSA POULIN | WWM | REVIEW | Approved | |
01/16/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
12/02/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
12/02/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Approved | |
12/02/2003 | DAN CASTRO | ZONING | REVIEW | Approved | |
12/11/2003 | JIM TATE | ENGINEERING | REVIEW | Approved | |
12/23/2003 | NEAL SAUNDERS | PLUMBING-COMMERCIAL | REVIEW | Approved | |
12/23/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T03CM05577 DENIED 12/11/03 1. Provide a disconnect for the Insta-Hot per NEC 422 Part C. 2. Load calculations total 333 > 279. Please re-check and correct as necessary. 3. Show available fault current at new location of Panel B, and rating of panel. |
12/23/2003 | NEAL SAUNDERS | MECHANICAL-COMMERCIAL | REVIEW | Approved |