Permit Number: T03CM05548
Parcel: 116123890

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM05548
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/26/2005 JOSE ORTIZ ENGINEERING REVIEW Approved
07/26/2005 HEATHER THRALL ZONING REVIEW Approved
08/10/2005 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS for Activity # T05CM03929 & T03CM05548

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, model energy and electrical. All code references are to the 2003 International Residential Code, 2000 International Energy Conservation Code, and Arizona State Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

All corrections and revisions shall be made on original tracings or finished reproducible set. Return this set and a copy along with a set of the first submission. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

All code references to the International Residential Code shall be changed from 2000 to 2003 with appropriate paragraph references: note #1, sheet 1; note #10, sheet 4; 8th note, sheet 8 and the electrical service diagram, sheet 8.

FOUNDATION PLANS:

1. Note that grade away from foundations shall comply with R401.3.

FLOOR PLANS:

1. Show that each water closet is located in a clear space not less than 30" wide (centered 15" from finished wall or fixture), figure R307.2.
2. Note that the landing at the front exit door shall not be more than 1.5" lower than the top of the threshold R311.4.3.
3. Correct the door jam size at the front exit door.

STRUCTURAL PLANS:

1. Provide manufacturer's calculations and data for pre-fabricated trusses, or note the requirement for deferred submittal to building inspector at installation.

SECTIONS - DETAILS - MISC. NOTES:

1. Ceiling gypsum board shall be either 5/8" or ½" sag resistant when applied to 24" o.c. framing, IRC table R702.3.5 footnote d.
2. Show a minimum 1" vent clearance between ceiling insulation and roof sheathing R806.3. This may be accomplished w/ baffles.

PLUMBING PLANS:

1. The City of Tucson has adopted the 1994 Uniform Plumbing Code with state amendments (ARIZONA STATE PLUMBING CODE). All plans must reference this code.
2. Correct the total fixture unit demand using 1994 UPC Table 6-3, water closet = 3, washer = 6 and hose bib = 3.
3. Plumbing vents shall be a minimum of 10 feet away from all air intakes (evap cooler) UPC 906.2.

MECHANICAL PLANS:

1. Gas appliances shall comply with ARIZONA STATE PLUMBING CODE combustion air requirements or Chapter 17, 2003 IRC. Show compliance for the W.H.
2. Provide an equipment specification list including the furnace and evap cooler.

ELECTRICAL PLANS:

1. Remove reference to the 2000 IRC at note #1.
2. The electrical amperage note at the main panels is not consistent with the service note below the load calculation and the electrical service diagram.
3. Indicate the location of all disconnect switches for air handling equipment.
4. Correct the smoke detector installation note to read 6" & 12" rather than 6' & 12'.

MODEL ENERGY CODE:
1. Provide energy calculations per the 2000 IECC and comply with IRC chapter 11, or apply 'Rescheck' (www.energycodes.gov/rescheck/).
2. The MEC energy calculations must support the "R" values and the "U" values shown.


If you have any questions, please contact your assigned plans examiner Ken Van Karsen at 791-5550, extension 1112.
08/14/2005 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/16/2005 CINDY AGUILAR OUT TO CUSTOMER Completed
08/16/2005 SUE REEVES REJECT SHELF Completed