Permit Number: T03CM05548
Parcel: 116123890

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM05548
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/08/2005 HEATHER THRALL ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Heather Thrall Senior Planner FOR: David Rivera Principal Planner

PROJECT: T03CM05548
1401 W. Saint Clair Street
Two (2) new single family residences
Site plan
1st Review
Transmittal date: April 8, 2005


COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. The square footage of the proposed residences on the submitted foundation and floor plans do not match the square footage calculations listed on the submitted site plan. Please address this discrepancy on the resubmitted drawings, listing the correct building square footage proposed.

2. On the resubmittal, please revise the building height note on the site plan to read maximum height of thirteen (13) feet - without the plus or minus notation.

3. On the submitted floor plan, a total of six (6) bedrooms are proposed for the site; three (3) for each unit. In turn, the number of bedrooms on a site dictates the number of parking spaces required for the project. Given six (6) bedrooms, five (5) parking spaces are required at minimum (Section 3.3.4 of the Land Use Code) for this project. On the submitted site plan, the five (5) required parking spaces provided are shown north, south and east of the buildings, with back up maneuvering shown onto North Cuesta Avenue and West Clair Street for each respective parking area. These parking areas, as shown, cannot be approved.

Per the Zoning Administrator's determination, any development requiring more than four (4) parking spaces must provide a parking lot area per Development Standard, Section 3.05. All parking and maneuvering must be on site. Section 3.05 describes parking lot requirements, including back up spurs and parking area access lane widths. Section 3.3.7.2 of the Land Use Code describes the allowed angles for parking spaces and their minimum required dimensions.

A copy of the Zoning Administrator's determination regarding parking requirements will be available the week of April 11, 2005.

On the resubmittal, please provide an on site parking lot for the proposed project that meets both LUC and DS code requirements. The alternatives are to reduce the number of bedrooms (see the LUC definition of bedroom in Section 6.2.2) or apply for and obtain a Board of Adjustment variance for the proposed parking configuration.

4. On the resubmitted site plan, please show the location(s) and provide the square footage of the total proposed vehicle use area(s), including parking and driveways. Please ensure this information is added to the lot coverage calculations and percentage listed on the revised site plan.

5. Be advised, these comments are not official comments for referral to the Board of Adjustment process. To obtain comments for the Board of Adjustment process, please revise the site plan to ensure all other comments are addressed, and contact me at 520-791-6508x1156 or via email at Heather.Thrall@tucsonaz.gov to make an office appointment.


If you have any questions about this transmittal, please call (520) 791-5608.
12/20/2004 TERRY STEVENS BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS for Activity T03CM05548 12/21/2004
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, model energy and electrical. All code references are to the 2003 International Residential Code, 2000 International Energy Conservation Code, and Arizona State Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

1. All corrections and revisions shall be made on the original tracings and two new sets of prints or (1) sepia & (1) blue line shall be returned along with all redline prints. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

FOUNDATION PLANS:
1. Note and detail minimum reinforcing, or provide code justification for alternate.
For stem-wall - one (1) #4 re-bar in the top of the stem.

FLOOR PLANS:
1. Identify ceiling heights in all areas on floor plan. If sloped ceiling, note average height.

SECTIONS - DETAILS - MISC. NOTES:
1. Wood sill plates shall be foundation grade redwood or pressure-treated wood per R320.---------see building cross section on 5 of 8

PLUMBING PLANS:
1. Provide a complete waste line plan. Show all vents, revents, waste lines and clean outs.-------missing from plan view
2. Provide an isometric drawing of waste lines (not required for single family residence). Show the size of waste lines, vents and required clean-outs.
3. Water line: Provide the total fixture unit demand and maximum developed length.
4. T&P line must terminate at the exterior between 6 and 24 inches above grade and must terminate facing down.

ELECTRICAL PLANS:
1. Range hood cannot be tied into appliance circuit
2. Note on plan that all electrical work shall comply with 2003 IRC chapters 33 - 42.

MODEL ENERGY CODE:
1. Provide energy calculations per the 1998 IECC and comply with IRC chapter 11.
2. Call out on the plan the "R" values of insulation, as well as the "U" values of the windows and doors in compliance with the energy calculations provided.

If you have any questions, please contact your assigned plans examiner Terry Stevens at 791-5550, extension 1112.

NOTE: As of 09/06/04 the City of Tucson has adopted the 2003 IRC with the exception of the plumbing portion which has been replaced with the Arizona state plumbing code.
12/27/2004 DOUG WILLIAMS ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/14/2005 CINDY AGUILAR OUT TO CUSTOMER Completed
04/14/2005 SUE REEVES REJECT SHELF Completed