Permit Number: T03CM05524
Parcel: 13419042D

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL TI

Permit Number - T03CM05524
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/18/2003 EROSE1 WWM REVIEW Needs Review
12/18/2003 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied SCOPE OF REVIEW:

The scope of this review covers Architectural, Structural, Plumbing, and Electrical. All features were checked only to the extent allowed by the submittal provided. All portions of the project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL:

q There are no general comments to be addressed.

ARCHITECTURAL:

q There are no architectural comments to be addressed.

STRUCTURAL:

q If special inspection is required as stated in the structural notes on Sheet S1.1, then provide a City of Tucson special inspection certificate for soils.

q Page 6 of the structural calculations indicates that Lintel LT2 is to be a double angle with a thickness of 5/16". Lintel LT2 in the schedule on Sheet S3.1 is indicated as 3/16" thick. Please correct.

q Page 11 of the structural calculations indicates that the large steel lintel is to have 6 bars total in the masonry at bearing. Sheet S2.1 shows 6 bars at the one bearing end, but only indicates 2 bars at the other bearing end. Please clarify. Other less stressed lintels have more bars calculated at the both ends then this lintel does at the one end.

PLUMBING:

q There are no plumbing comments to be addressed.

ELECTRICAL:

q There are no electrical comments to be addressed.

-End of Review-
12/18/2003 EROSE1 WATER REVIEW Needs Review
12/18/2003 EROSE1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/18/2003 ELAINE ROSE OUT TO CUSTOMER Completed