06/15/2004 Neil Saunders BUILDING-RESIDENTIAL REVIEW Denied Plan Check Comments - Project T03CM05523

Plan Review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

General Requirements

1. All corrections and revisions shall be made on the original tracings and two new sets of prints or (1) sepia and (1) blue line shall be returned.
2. Pen or pencil corrections on final prints will not be acceptable. To avoid delays ensure that corrections have been made, are complete and have been coordinated on all-applicable details and notes.

Site Plan

1. Show water and sewer lines on property.

Structural Plans

1. New footings on foundation plan are required to be 16".
2. Carport beam (4x6) is inadequate for the span and tributary loads. Resize
3. Detail 1: Simpson 128T has no load capacity. Use 1212HT on each side.
4. Detail 2: Provide H2.5 from top plate to rafters.
5. Detail 5: AB44 is not rated for uplift.
6. Roof Plan (pg A2) over foyer: Callout detail 3/A3 is incorrect.
7. Callout header sizes on framing plan
8. Clarify "(E) 4" wall". Double wythe? Details 3 & 9 and section.