Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2004 JIM EGAN FIRE REVIEW Denied 1. An approved fire apparatus access roadway must be provided and extended to within 150 feet of all portions of the exterior walls of all structures. (See 2000 IFC Sec. 503.)

2. Fire lane signs required.
12/09/2003 Patricia Gilbert ENGINEERING REVIEW Denied DATE: December 12, 2003
ACTIVITY NUMBER: T03CM05514
PROJECT NAME: Patricia Gilbert
PROJECT ADDRESS: 105 East Yavapai Road
PROJECT REVIEWER: Patricia Gilbert, Engineering Associate

The following items must be revised or added to the site plan. Please include a response letter with the next submittal that states how all comments have been addressed.

RESUBMITTAL REQUIRED: SITE PLAN
APPROVAL: DRAINAGE REPORT


1. Provide a dimension for the ingress/egress from Yavapai Road. DS 2-02.2.1.A.11.

2. A minimum setback distance of five (5) feet for a pedestrian refuge area must be maintained between any enclosed structure and a PAAL. The refuge area may have a roof for shade, provided it contains a sidewalk and pedestrian access which is unobstructed and is set back one (1) foot from the PAAL. Sidewalk is required adjacent and parallel to any PAAL on the side where buildings are located. Provide a sidewalk and pedestrian refuge between existing drive and existing three bedroom apartment. Revise plan as necessary. DS 3-05.2.2.B.1., Figure 1 and DS 2-08.4.1.B.

3. Sidewalks must be flood free for up to the 10-yr. event. Add a note on the plan, "All roof down spouts on all structures must be routed under any adjacent sidewalk." DS 2-08.4.1.E

4. Provide estimate cut and fill quantities to the site and grading plan. DS 2-02.2.1.A.17.

5. Provide dimensions from street centerline to existing curbs. DS 2-02.2.1.A.21.

6. All new subdivisions and applications for building permits shall provide four (4) foot wide sidewalks along the entire length of street frontage, whether public or private. Is there currently sidewalk along Yavapai Road? If there is sidewalk please dimension and label existing sidewalk. If sidewalk is not existing within the ROW, provide a 4' sidewalk within the ROW. DS 2-02.2.1.A.21., DS 3-01.3.3.A.

7. Each service area is required to have a clear approach of fourteen (14) feet by forty (40) feet for the collection vehicle. The maximum back-up distance for the collection vehicle shall be forty (40) feet. Currently this plan has the collection vehicle backing up more than 40 feet. Revise plan accordingly or get written approval from John Clark (Environmental Services 791-3175 ext. 1136) for the current position of the trash enclosure. DS 6-01.4.1.C

8. Please a note on the Site Plan sheet C1.1, see Grading Plan sheet C1.2 for elevation information, drainage patterns and finsih floor elevations (FFE).
12/24/2003 David Rivera HANDICAP-SITE REVIEW Approved
12/24/2003 David Rivera ZONING REVIEW Denied DSC TRANSMITTAL

FROM: David Rivera Senior Planner

FOR: Patricia Gehlen
Principal Planner

PROJECT: T03CM05514 - Yavapai Apartments
105 East Yavapai Road
Site Plan Multi-family Apartments

Transmittal date: 1st Review December 24, 2003

COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. All parking spaces that abut a sidewalk must be provided with wheel stops or the sidewalk must be constructed to a width of six and one-half feet. Add to keynote 24 "Typical all parking stalls" or show wheel stops at all parking stalls. DS 2-02.2.1.A.8

2. Dimension the width of the pedestrian refuge area between the PAAL and the three-bedroom apartment. See redlines. Minimum width required is five feet. DS 2-02.2.1.A.12

3. If applicable indicate the location, type, and size of existing or proposed freestanding signage. DS 2-02.2.1.A.13

4. If applicable all existing or proposed easements must be shown on the plan along with docket and page reference. DS 2-02.2.1.A.20

5. Dimensions from street monument lines to existing and proposed curbs, sidewalks. DS 2-02.2.1.A.21

6. If applicable indicate on the plan the location or layout of existing or proposed freestanding lighting. DS 2-02.2.1.A.25

7. See landscape reviewer comments regarding the requirements for landscape borders, NPPO and screening. DS 2-02.2.1.A.27

8. Under the LUC Project Data text block add the words "Multi-family", also please add the LUC subject to section 3.5.7.1.F. DS 2-02.2.1.A.31

9. Include under the LUC Project Data text block the square footage of the vehicular use area. DS 2-02.2.1.A.

If you have any questions about this transmittal, please call David Rivera, (520) 791-5608.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan
12/30/2003 JOE LINVILLE NPPO REVIEW Denied Revise the grading and native plant preservation plans as necessary to eliminate conflicts.
12/30/2003 Joseph Linville LANDSCAPE REVIEW Denied 1) Screening is required for the vehicular use areas per LUC Table 3.7.2-I. Specifically, a five foot high masonry wall is required where the vehicular use area is located within 100 feet of adjacent residentially zoned property.

2) A five foot high screen is required to screen the parking area adjacent Yavapai Road. Required screens are to be located outside of any sight visibility triangles. LUC 3.7.3.4

3) Revise the grading plans to accomodate trees designated as preserved-in-place. The root zone for protected plants should remain undisturbed as noted on sheet N1.2.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/06/2004 TAMI ACHONG OUT TO CUSTOMER Completed