Permit Number: T03CM05507
Parcel: 119180890

Address:
3672 S 16TH AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM05507
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/24/2003 JIM EGAN FIRE REVIEW Approved
11/24/2003 DAN CASTRO ZONING REVIEW Approved
11/24/2003 BLANCA ESPINO ENGINEERING REVIEW Approved
11/25/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide pressure calculations to show how water piping was sized.
2. Provide water riser diagram.
3. Add janitor's sink.
4. Add drain and cleanout for electric drinking fountain.
11/25/2003 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
11/25/2003 ROBERT SHERRY WATER REVIEW Approved
11/25/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved DENIED 11/25/03
Re-work Load Summary.
11/25/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise ventilation to conform to requirements of Section 403, IMC 2000.
11/26/2003 GERRY KOZIOL WWM REVIEW Approved