Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T03CM05469
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/22/2004 | Robert Sherry | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the water supply calculations. Use Appendix A of the 1994 UPC. The minimum water pressure for the longest branch is approximately 35 psig (the ice cuber (#23) requires 20 psig plus 15 psig for the backflow preventer). Your calculated pipe length appears to be less than shown on the drawings. Adjust the pipe sizing as required. 2. The maximum water velocity in copper piping is limited by the IAPMO Installation Standard, IS 3-93, to a range of 5 to 8 feet per second. Reference Section A6.1, UPC 1994. 3. Provide upper terminal cleanouts for hand sinks (P-8) at the bar and for the South urinal (P-3). Reference Section 707.4, UPC 1994. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/28/2004 | EGRANT1 | OUT TO CUSTOMER | Completed |
| 04/23/2004 | SUE REEVES | REJECT SHELF | Completed |