Permit Number: T03CM05469
Parcel: 133369570

Address:
68 N HARRISON RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM05469
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/22/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide calculations demonstrating the provided ventilation complies with Sections 403.3 and 403.2, IMC 2000. Provided calculations incomplete, revise and resubmit. Show how the number of occupants used in the calculations for each area relates to the occupancy load shown in Table 403.3.
2. Provide signature for Arizona seal on sheet M-1.3.
03/22/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Provide signature for Arizona seal on sheet P-1.0, P-3.0, and FP1.0.
2. Sheet P-2.0 not included in review set. Provide calculations showing water supply piping is sized in accordance with Section 610.4, UPC 1994. The calculations provided are incomplete. Include the data referenced in Section 610.7 if using Table 6-4. If using Table 6-4, the fixture units for flushometer valves must be calculated using the method shown in Section 610.10, UPC 1994. The hot water pipes are to be sized using the method shown in Sections 610.12 or 610.13, UPC 1994. Head losses (e.g. meter loss, RPBP loss, and lift) must be subtracted from the available water pressure prior to using Table 6-4.
3. Sheet P-2.0 not included in review set. Include all fixtures when calculating the total demand and determining pipe sizes. (See note in Table 6-3: "Water supply outlets for items not listed above shall be computed at their maximum demand but in no case less than:…") Reference Section 610.1, UPC 1994.
4. Provide a vent for each fixture trap. (e.g. the funnel drain and P-2 in center portion of the Women's restroom) Reference Sections 901.0 and 910.0, UPC 1994.
5. Comment not addressed. Provide upper terminal cleanouts on horizontal drainage pipe. See exception (1) of Section 707.4, UPC 1994. (e.g. the floor sink south of column B-4, urinals and all sinks.)
04/13/2004 Martin Haeberle BUILDING-COMMERCIAL REVIEW Denied Provide termite resistant wood for proposed flooring in contact with concrete.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/15/2004 CINDY AGUILAR OUT TO CUSTOMER Completed
04/14/2004 SUE REEVES REJECT SHELF Completed