Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T03CM05469
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/22/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide calculations demonstrating the provided ventilation complies with Sections 403.3 and 403.2, IMC 2000. Provided calculations incomplete, revise and resubmit. Show how the number of occupants used in the calculations for each area relates to the occupancy load shown in Table 403.3. 2. Provide signature for Arizona seal on sheet M-1.3. |
| 03/22/2004 | Robert Sherry | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide signature for Arizona seal on sheet P-1.0, P-3.0, and FP1.0. 2. Sheet P-2.0 not included in review set. Provide calculations showing water supply piping is sized in accordance with Section 610.4, UPC 1994. The calculations provided are incomplete. Include the data referenced in Section 610.7 if using Table 6-4. If using Table 6-4, the fixture units for flushometer valves must be calculated using the method shown in Section 610.10, UPC 1994. The hot water pipes are to be sized using the method shown in Sections 610.12 or 610.13, UPC 1994. Head losses (e.g. meter loss, RPBP loss, and lift) must be subtracted from the available water pressure prior to using Table 6-4. 3. Sheet P-2.0 not included in review set. Include all fixtures when calculating the total demand and determining pipe sizes. (See note in Table 6-3: "Water supply outlets for items not listed above shall be computed at their maximum demand but in no case less than:…") Reference Section 610.1, UPC 1994. 4. Provide a vent for each fixture trap. (e.g. the funnel drain and P-2 in center portion of the Women's restroom) Reference Sections 901.0 and 910.0, UPC 1994. 5. Comment not addressed. Provide upper terminal cleanouts on horizontal drainage pipe. See exception (1) of Section 707.4, UPC 1994. (e.g. the floor sink south of column B-4, urinals and all sinks.) |
| 04/13/2004 | Martin Haeberle | BUILDING-COMMERCIAL | REVIEW | Denied | Provide termite resistant wood for proposed flooring in contact with concrete. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/15/2004 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 04/14/2004 | SUE REEVES | REJECT SHELF | Completed |