Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T03CM05469
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/03/2004 | Robert Sherry | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide calculations demonstrating the provided ventilation complies with Sections 403.3 and 403.2, IMC 2000. Provided calculations incomplete, revise and resubmit. 2. Provide listing information and show installation details for the insulation to be installed around the grease duct as indicated on sheet M1.1. Reference Section 506.3.11 (1), IMC 2000. The grease duct is shown on the mechanical drawings and is not part of the hood. 3. Provide structural calculations and details to show that the Type I hood is supported in accordance with Section 507.6, IMC 2000. Not received. 4. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top units. Reference Section 1604, IBC 2000. Not received. 5. If make-up air is being provided for the Type I hood by the rooftop units, provide electrical interlock to ensure that makeup air is provided whenever the exhaust system is in operation. Reference Section 508.1, IMC 2000. |
| 02/03/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Termination of the excess pressure relief from the water heater over a floor drain will require a funnel top to prevent splashing. Reference Section 804.1, UPC 1994. 2. Provide calculations showing water supply piping is sized in accordance with Section 610.4, UPC 1994. The calculations provided are incomplete. Include the data referenced in Section 610.7 if using Table 6-4. If using Table 6-4, the fixture units for flushometer valves must be calculated using the method shown in Section 610.10, UPC 1994. The hot water pipes are to be sized using the method shown in Sections 610.12 or 610.13, UPC 1994. Head losses (e.g. meter loss, RPBP loss, and lift) must be subtracted from the available water pressure prior to using Table 6-4. 3. Include all fixtures when calculating the total demand and determining pipe sizes. (See note in Table 6-3: "Water supply outlets for items not listed above shall be computed at their maximum demand but in no case less than:…") Reference Section 610.1, UPC 1994. 4. Provide a vent for each fixture trap. (e.g. floor sinks serving P-11, P-2 in southwest portion of Women's restroom) Reference Sections 901.0 and 910.0, UPC 1994. 5. Provide upper terminal cleanouts on horizontal drainage pipe. See exception (1) of Section 707.4, UPC 1994. 6. Resize vent piping to conform to Table 7-5, UPC 1994. A maximum of 24 fixture units are allowed for a 2" vent. |
| 02/05/2004 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Cooler addition and patio are not included in the allowable area calculations. Revise calculations. Note: Did not amend code analysis sheet. Actual area exceeds allowable area. 2. Provide structural calculations and framing plan for raised floor. Note: floor live load to utilize a minimum of 100 psf. Reference Table 1607.1 IBC. Submitted sheet does not constitute calculations or a framing plan. Please seal all construction documents on resubmits. 3. If cooler addition and patio are included in the scope of work for this permit include plans and structural calculations. If not, annotate on plans. Please note on plans 4. Provide design and calculations for additional loads placed on roof by new equipment. See Mechanical Comments. This application can not be approved until a separate permit indicated in response letter is obtained. 5. Provide design and calculations for attachment to structure by the proposed hood. See Mechanical Comments. This application can not be approved until a separate permit indicated in response letter is obtained. 6. Patio area exits are part of the egress system. Provide details for gate hardware and number of occupants serving these gates. Note include occupants from egress doors opening into this area from the rest of the building. Reference sections 1003.2.2.10 and 1003.3.1.9 IBC. Please provide details previously requested. 7. Include method of anchoring walls. Sheet A-5.0 was not included in resubmitted plans. |
| 02/18/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/03/2004 | EGRANT1 | OUT TO CUSTOMER | Completed |
| 02/23/2004 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |