Permit Number: T03CM05450
Parcel: 12218262A

Review Status: Completed

Review Details: OTHER

Permit Number - T03CM05450
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2004 MICHAEL ST. PAUL ZONING REVIEW Denied Building plans must have site plan approval.
12/16/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT LBUCZYN1@CI.TUCSON.AZ.US
IF YOU CARE TO DISCUSS.

1. Per Table 250-66, 500 MCM Service Entrance Conductors need 1/0 GEC. We cannot "grandfather" Code violations, so even if the #4 is existing, it should be changed.
2. Please indicate how the feeder to the new panel is to be connected in the existing disconnect. New conductors to New Panel are not protected at their source of supply per NEC 240-21. Note that these conductors are do not appear to be tapped from a feeder as defined in the Electrical Code, and thus would not fall under the "tap rule" in (b) of 240-21.
3. Please address Available Fault current. Notes 6-9 call for series rating. However, there is no upstream device shown in the existing disconnect on the plans. If TEP can not provide AFC in a timely fashion for design, suggest a note requiring the Contractor to follow up for this verification.
12/22/2003 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/08/2004 LISA LESNY OUT TO CUSTOMER Completed