| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/09/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Complete and sign/seal energy calculations. 2. Provide balancing dampers for ductwork. Reference Section 603.15, IMC 2000. 3. Revise mechanical note #9/A3: it is in conflict with detail A/A4. |
| 04/09/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 04/14/2004 | PATRICIA GEHLEN | ZONING | REVIEW | Approved | |
| 04/14/2004 | DROBEY1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 04/14/2004 | JIM TATE | ENGINEERING | REVIEW | Approved | |
| 04/14/2004 | DROBEY1 | FIRE | REVIEW | Needs Review |