Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T03CM05439
Parcel: 120052730

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM05439
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/09/2004 DROBEY1 FIRE REVIEW Needs Review
04/09/2004 DROBEY1 WWM REVIEW Passed
04/09/2004 DROBEY1 BUILDING-COMMERCIAL REVIEW Needs Review
04/09/2004 DROBEY1 ZONING REVIEW Needs Review
04/09/2004 DROBEY1 ENGINEERING REVIEW Needs Review
11/17/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show sizes of roof drain and overflow along with drain leader sizes.
2. Show separate drain leaders from roof drain and overflow.
11/17/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
11/17/2003 ROBERT SHERRY WATER REVIEW Approved
11/17/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Ventilation rate for first floor retail spaces is 0.3 CFM/SF, not 0.2 CFM/SF. Reference Section 403.3, IMC 2000.
2. Provide energy calculations.
3. Show size, routing, and termination of condensate drain.