Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T03CM05439
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/09/2004 | DROBEY1 | FIRE | REVIEW | Needs Review | |
04/09/2004 | DROBEY1 | WWM | REVIEW | Passed | |
04/09/2004 | DROBEY1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
04/09/2004 | DROBEY1 | ZONING | REVIEW | Needs Review | |
04/09/2004 | DROBEY1 | ENGINEERING | REVIEW | Needs Review | |
11/17/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show sizes of roof drain and overflow along with drain leader sizes. 2. Show separate drain leaders from roof drain and overflow. |
11/17/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
11/17/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
11/17/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Ventilation rate for first floor retail spaces is 0.3 CFM/SF, not 0.2 CFM/SF. Reference Section 403.3, IMC 2000. 2. Provide energy calculations. 3. Show size, routing, and termination of condensate drain. |