Permit Number: T03CM05438
Parcel: 11615087J

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE ONLY

Permit Number - T03CM05438
Review Name: COMMERCIAL-BLDG/FIRE ONLY
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/17/2003 MICHAEL ST. PAUL ZONING REVIEW Approved
12/02/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
12/03/2003 JIM EGAN FIRE REVIEW Approved
12/09/2003 Martin Haeberle BUILDING-COMMERCIAL REVIEW Denied 1. Provide listed method to be used for fire penetrations.
2. Show emergency lighting at all doors using delayed locking mechanism. Reference section 1003.3.1.8.2 IBC
3. Clearly identify location of all doors recieving delayed egress locks
4. Plans indicate areas where occupants have to pass threw more than one delayed egress to reach the exit. Reference section 1003.3.1.8.2 IBC

Final Status

Task End Date Reviewer's Name Type of Review Description
12/10/2003 TAMI ACHONG OUT TO CUSTOMER Completed
12/10/2003 ANGIE SHOFFSTALL REJECT SHELF Completed