Permit Number: T03CM05436
Parcel: 12701005D

Review Status: Stopped

Review Details: COMMERCIAL TI

Permit Number - T03CM05436
Review Name: COMMERCIAL TI
Review Status: Stopped
Review Date Reviewer's Name Type of Review Description Status Comments
06/02/2004 EROSE1 BUILDING-COMMERCIAL REVIEW Stop
11/17/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
11/17/2003 ANY FIRE REVIEW Stopped
11/17/2003 ANY WWM REVIEW Stopped
11/17/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved Had been denied 11/03/03 under Activity Number T03EL02168. Had one office meeting and one over-the-counter in way of followup, as well as 2 emails.
11/17/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide equipment data for air conditioners.
2. Show structural support of A/C units.
3. Provide sizing calculations for condensate drains,
4. Show how auxiliary/secondary condensate drains are being provided.
5. Show chilled water piping.
6. Show how ventilation is being maintained in this area (including quantity).
11/17/2003 DAN CASTRO ZONING REVIEW Approved
11/17/2003 ROBERT SHERRY WATER REVIEW Approved
11/17/2003 ANY ENGINEERING REVIEW Stopped

Final Status

Task End Date Reviewer's Name Type of Review Description
11/17/2003 ANY APPROVAL SHELF Stopped
11/17/2003 ANY OUT TO CUSTOMER Stopped
11/17/2003 ANY REJECT SHELF Stopped