Permit Review Detail
Review Status: Stopped
Review Details: COMMERCIAL TI
Permit Number - T03CM05436
Review Name: COMMERCIAL TI
Review Status: Stopped
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/02/2004 | EROSE1 | BUILDING-COMMERCIAL | REVIEW | Stop | |
| 11/17/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 11/17/2003 | ANY | FIRE | REVIEW | Stopped | |
| 11/17/2003 | ANY | WWM | REVIEW | Stopped | |
| 11/17/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | Had been denied 11/03/03 under Activity Number T03EL02168. Had one office meeting and one over-the-counter in way of followup, as well as 2 emails. |
| 11/17/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide equipment data for air conditioners. 2. Show structural support of A/C units. 3. Provide sizing calculations for condensate drains, 4. Show how auxiliary/secondary condensate drains are being provided. 5. Show chilled water piping. 6. Show how ventilation is being maintained in this area (including quantity). |
| 11/17/2003 | DAN CASTRO | ZONING | REVIEW | Approved | |
| 11/17/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/17/2003 | ANY | ENGINEERING | REVIEW | Stopped |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/17/2003 | ANY | APPROVAL SHELF | Stopped |
| 11/17/2003 | ANY | OUT TO CUSTOMER | Stopped |
| 11/17/2003 | ANY | REJECT SHELF | Stopped |