Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T03CM05432
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/17/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
| 11/17/2003 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 11/17/2003 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
| 11/18/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 11/18/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T03CM05432 DENIED 11/18/03 1. Provide load calculations to demonstrate that 400 A service is adequate. 2. Provide IECC calculations for interior lighting power budget, unless this building was constructed before 1994. |
| 11/18/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/18/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 11/19/2003 | ANY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/19/2003 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/19/2003 | MONICA VALDEZ | OUT TO CUSTOMER | Completed |