| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/14/2003 | JIM EGAN | FIRE | REVIEW | Approv-Cond | Fire approval for "Office Building" only. |
| 11/14/2003 | ANY | BUILDING-COMMERCIAL | REVIEW | Denied | SEE COMMENTS ON BACK OF APPLICATION. |
| 12/11/2003 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 12/12/2003 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
| 12/12/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T03CM05417 DENIED 11/14/03 There was an annotation added to the plans, which appeared to be added manually. Not signed, initialed, or dated, not Revision Number. It calls for (3) 3/0 and (1) #6 GND between the meter base and the Service Panel "B". With no OC device on the line side of the Service Panel, the GND, if present, would be sized according to the phase conductors per NEC 250-102 (c) and Table 250-66. Also, since the "Service Panel" would be the location of the disconnect and hence a Main Bonding Jumper per NEC 250-28, the fourth wire in the run should be the Grounded conductor. NEC 250-24 (b) requires the Grounded Conductor to be brought to the Service equipment. Having the GND as well would consist of a parallel path to ground on the load side of that disconnect. LAB 791.5550 x1106 |