| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/14/2003 | ANY | BUILDING-COMMERCIAL | REVIEW | Denied | SEE COMMENTS ON BACK OF APPLICATION. |
| 11/14/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T03CM05416 DENIED 11/14/03 1. Demand calculations do not allow application to AC units. 2. Demand calculations do not start just above 1 KW. 3. Provide line diagram. There is a concern about the 60/2 CB feeding Sub-Panels B & C on just one CB. 4. Concur with the Sturctural Plans Examiner that these plans shall be produced by a Registrant. |
| 11/14/2003 | BLANCA ESPINO | ENGINEERING | REVIEW | Z_DO NOT USE | |
| 11/14/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
| 12/05/2003 | MVALDEZ1 | ZONING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/05/2003 | MONICA VALDEZ | OUT TO CUSTOMER | Completed |