Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T03CM05416
Parcel: 11106191A

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE ONLY

Permit Number - T03CM05416
Review Name: COMMERCIAL-BLDG/FIRE ONLY
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/14/2003 ANY BUILDING-COMMERCIAL REVIEW Denied SEE COMMENTS ON BACK OF APPLICATION.
11/14/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T03CM05416 DENIED 11/14/03
1. Demand calculations do not allow application to AC units.
2. Demand calculations do not start just above 1 KW.
3. Provide line diagram. There is a concern about the 60/2 CB feeding Sub-Panels B & C on just one CB.
4. Concur with the Sturctural Plans Examiner that these plans shall be produced by a Registrant.
11/14/2003 BLANCA ESPINO ENGINEERING REVIEW Z_DO NOT USE
11/14/2003 JIM EGAN FIRE REVIEW Approved
12/05/2003 MVALDEZ1 ZONING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/05/2003 MONICA VALDEZ OUT TO CUSTOMER Completed