Permit Number: T03CM05413
Parcel: 120075380

Address:
4407 S 12TH AV

Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - T03CM05413
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/19/2004 Loren Makus ENGINEERING REVIEW Approved
02/20/2004 Peter McLaughlin ZONING REVIEW Denied SITE PLAN TRANSMITTAL

TO: Jeffrey A. Stanley
3409 W. Green Ridge
Tucson, AZ 85741
(520) 299-8700

FROM: Peter McLaughlin
Sr. Planner

FOR: Patricia Gehlen
Principal Planner
Development Services Dept.

PROJECT:
T03CM01898
Dabboy's Auto
4407 S. 12th Avenue
Change of Use
Site Plan Review (2nd review)

TRANSMITTAL: February 23, 2004


COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Show the wheelstop to be provided for the easternmost parking space (closest to the building). Also, place the 2-½ foot dimension for the wheelstops at the front (wheel side) instead of the back.
DS 3-05.2.3

2. The future sight visibility triangle is not shown correctly. The SVT stem dimension must be shown at 20 feet from face of future curb.
DS 2-02.2.1.A.10
DS 3-01.5.2.B.4

3. Provide a future plan for approval showing how the site will meet code for all requirements, including parking and landscaping, after time of 12th Avenue widening. It appears that at least one parking space will be lost when MS&R right-of-way can no longer be used as part of the site.
LUC 2.8.3.5.F

4. As stated in the response comments these lots are to be combined with an Assessors tax combo form and a recorded covenant which can be obtained from the zoning review counter. Please provide documentation of lot combination.
DS 2-02.2.1.A.2

5. A five-foot wide pedestrian refuge area with a minimum four-foot wide sidewalk is required between the PAAL and the existing enclosed buildings. The refuge areas must include a four-foot wide concrete sidewalk that is physically separate from the PAAL. The sidewalk /stps profided do not extend along the perimeter of the building where it is adjacent to vehicular use area/PAAL.
DS 3-05. 2.1.C.1
DS 3-05.2.2.B.1
DS 2-02.2.1.A.12

6. The location of vehicle display parking as show along the north side of the building does not allow vehicles to maneuver into and out of customer and h/c spaces shown. A minimum 24-foot PAAL and 3-foot backup spur is required behind the required customer parking spaces. Revise drawing accordingly.
LUC 3-05
LUC 3.3.7.2

If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608.
02/23/2004 PETER MCLAUGHLIN HANDICAP-SITE REVIEW Approved
02/24/2004 Andrew Connor LANDSCAPE REVIEW Denied 1) Temporary use of the MS&R right of way area is allowed for excess parking and to temporarily meet landscape requirements. The site and landscape plans are required to show how the project will comply with all LUC requirements when the MS&R setback zone can no longer be used as part of the site. LUC 2.8.3.5.F
Revise as necessary.

Upon conditional approval of the MS&R site and landscape plans, a covenant per LUC 2.8.3.5.F is required to be recorded along with a copy of the approved plans. Add this recording information to the site plans. See http://www.ci.tucson.az.us/dsd/Major_Streets_Covenant.pdf for an acceptable covenant.


2) ) Revise the landscape plan to include only plants types which do not typically exceed thirty inches in height within the current and future sight visibility triangles along Twelfth Avenue. Revise related notes as necessary. DS 2-06.3.8.F

3) Provide a barrier per DS 3-05.2.3.C.1 and LUC 3.7.2.3.B between the street landscape borders and vehicular use areas on the site.

4) Revise the landscape plan to include the Parkinsonia shown as preserved in place on the site plan.
DS 2-07.2.2

Final Status

Task End Date Reviewer's Name Type of Review Description
02/25/2004 CINDY AGUILAR OUT TO CUSTOMER Completed
02/24/2004 ANGIE SHOFFSTALL REJECT SHELF Completed