Permit Number: T03CM05410
Parcel: 133452230

Address:
35 N HOUGHTON RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM05410
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/07/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. The provided Public Sewer Plan shows the size and route of the building sewer but the building sewer does not comply with Section 719.1, UPC 1994.
2. Comment not addressed. Provide a fixture description for the water closet. The model number shown for the new fixture (Zurn Z5650) is for a flush valve, not a water closet. Show the minimum operating pressure for the new water closet. Reference Section 401.1, UPC 1994.
04/07/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the ventilation calculations using the occupant loads from Table 403.3, IMC 2000. Reference Section 403, IMC 2000. Show the calculations on the sheet. Reference Section 106.3.1, IMC 2000.
04/15/2004 GERRY KOZIOL WWM REVIEW Denied Need to show location/method of connection to public sewer. May need to build on-site private sewer for Eastpoint Commercial Center (with DEQ review/approval). Need copy of on-site private sewer - manhole or tap permit?
04/28/2004 David Rivera ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/29/2004 LISA LESNY OUT TO CUSTOMER Completed
04/28/2004 ANGIE SHOFFSTALL REJECT SHELF Completed