Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T03CM05397
Review Name: OTHER
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/17/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | The minimum exhaust flow rate for restrooms is 75 CFM per water closet or urinal. |
11/17/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Coordinate the waste riser diagram with the plumbing plan in the area of the new floor sink. 2. Clarify scale of plumbing plan. If it is correct, the trap arm of the relocated lavatory is too long. 3. Provide calculations to show how the water piping was sized. |
11/17/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
12/03/2003 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/28/2003 | ANGIE SHOFFSTALL | OUT TO CUSTOMER | Completed |