Permit Number: T03CM05397
Parcel: 14029007C

Review Status: Completed

Review Details: OTHER

Permit Number - T03CM05397
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/17/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied The minimum exhaust flow rate for restrooms is 75 CFM per water closet or urinal.
11/17/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Coordinate the waste riser diagram with the plumbing plan in the area of the new floor sink.
2. Clarify scale of plumbing plan. If it is correct, the trap arm of the relocated lavatory is too long.
3. Provide calculations to show how the water piping was sized.
11/17/2003 ROBERT SHERRY WATER REVIEW Approved
12/03/2003 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/28/2003 ANGIE SHOFFSTALL OUT TO CUSTOMER Completed