Permit Number: T03CM05363
Parcel: 113102270

Address:
1534 E SILVER ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T03CM05363
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/13/2003 GERRY KOZIOL WWM REVIEW Approved
12/04/2003 Bruce Stevens BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS PROJECT #T03CM05363
12/09/2003 1534E. SILVER ST.

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.
SITE PLAN:
1. INDICATE THE LOCATION OF GAS METER AND YARD LINE ON SITE PLAN.

FLOOR PLANS:
1. LOCATE AND IDENTIFY BRACE WALL TYPES AND LOCATIONS. PROVIDE NAILING SCHEDULE.

STRUCTURAL PLANS:
1. SPECIFY DESIGN CRITERIA ON PLANS. VALUES FOR FLOOR DEAD LOAD AND LIVE LOAD, ROOF DEAD LOAD AND LIVE LOAD.
2. PROVIDE COMPLETE ROOF FRAMING PLAN. SHOW HOW RIDGE BEAM (B12) IS TO BE SUPPORTED.
3. PROVIDE BRACING DETAILS AND NOTES FOR EXTERIOR FRAME WALLS AND MAIN CROSS-STUD PARTITIONS, OR USE FULLY BRACED, PER R602.10.3. A MINIMUM PANEL WIDTH OF 48" IS REQUIRED TO EFFECTIVELY BRACE THE PARTITION. SEE TABLE R602.10.3, CATEGORY "C". IF BRACING DOES NOT COMPLY, PROVIDE A LATERAL ANALYSIS OR ALTERNATE DESIGN TO BE REVIEWED BY THE PLANS EXAMINER. WIND FORCES FOR SINGLE STORY RESIDENCES SHALL USE 90 MPH, EXPOSURE "B". TWO STORY RESIDENCES OR AREAS OF HIGHER WIND SHALL USE EXPOSURE "C".

ELEVATIONS:
1. NOTE GLASS IN HAZARDOUS AREAS SHALL BE SAFETY GLASS PER R308.4. ALL GLASS WITHIN 2' OF EITHER EDGE OF DOORS SHALL BE SAFETY GLAZED.
SECTIONS - DETAILS - MISC. NOTES:
1. WOOD SILL PLATES SHALL BE FOUNDATION GRADE REDWOOD OR PRESSURE-TREATED WOOD PER R324.
PLUMBING PLANS:
1. PROVIDE PRESSURE AND TEMPERATURE RELIEF VALVE AT WATER HEATER.
MECHANICAL PLANS:
1. THE DWELLING MUST BE PROVIDED WITH HEATING CAPABLE OF MAINTAINING A ROOM TEMPERATURE OF 68 DEGREES AT A POINT 3' ABOVE THE FLOOR PER R303.6. SHOW SOURCE OF HEAT.
IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
BRUCE STEVENS @ 791-5550 EXT. 1174

Final Status

Task End Date Reviewer's Name Type of Review Description
12/11/2003 TAMI ACHONG OUT TO CUSTOMER Completed
12/10/2003 ANGIE SHOFFSTALL REJECT SHELF Completed