Permit Number: T03CM05355
Parcel: 137055220

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM05355
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/12/2003 JIM EGAN FIRE REVIEW Approved
11/12/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show waste connection for sink on waste and vent schematic.
2. Show that the floor sink will be installed in a location that will be readily accessible for inspection and cleaning. Reference Section 804.1, UPC 1994.
3. The minimum font size for drawings is 10 points.
11/12/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
11/12/2003 ROBERT SHERRY WATER REVIEW Approved
11/12/2003 DAN CASTRO ZONING REVIEW Approved
11/12/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide calculations to show that the project area has adequate ventilation. Reference Section 403.3, IMC 2000.
11/18/2003 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
12/04/2003 MELISSA POULIN WWM REVIEW Approved
12/04/2003 BLANCA ESPINO ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/05/2003 LISA LESNY OUT TO CUSTOMER Completed