Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/12/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
11/12/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show waste connection for sink on waste and vent schematic. 2. Show that the floor sink will be installed in a location that will be readily accessible for inspection and cleaning. Reference Section 804.1, UPC 1994. 3. The minimum font size for drawings is 10 points. |
11/12/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
11/12/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
11/12/2003 | DAN CASTRO | ZONING | REVIEW | Approved | |
11/12/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide calculations to show that the project area has adequate ventilation. Reference Section 403.3, IMC 2000. |
11/18/2003 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
12/04/2003 | MELISSA POULIN | WWM | REVIEW | Approved | |
12/04/2003 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved |