Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T03CM05339
Parcel: 12405007B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM05339
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/10/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
11/10/2003 ROBERT SHERRY WATER REVIEW Approved
11/10/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
11/13/2003 JIM EGAN FIRE REVIEW Approved
11/13/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T03CM05339 - DENIED - 11/10/03 - 791.5550 x1106
1. Provide schedule for lighting fixtures. Show voltage, wattage, number of bulbs, and volt-amprers.
2. Provide short circuit rating on Panel A. One-phase, three wire is not a short circuit rating.
3. If the "1-phase 3W" refers to this panel, note that the panel schedule is set up as a three phase panel, not single phase. And with a neutral conductor, this can not be 3-wire, but 4.
4. Also note that Phase A calculates out to be 9980 volt-amperes, not 7100.
5. Indicate whether the circuit breakers for the new circuits are to be new, or if they are existing. They may have to be addressed as to available fault current at the panel.

DENIED - 11/12/03
1. Circuit 20, when continuous load is considered, shall be 960 VA.
2. Circuit 19, when continuous load is considered, shall be 320 VA.
3. See Comment #4, from Comments dated 11/10/03.
11/14/2003 LLESNY1 WWM REVIEW Passed
11/14/2003 MICHAEL ST. PAUL ZONING REVIEW Approved
11/14/2003 ANY BUILDING-COMMERCIAL REVIEW Approved
11/14/2003 BLANCA ESPINO ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/14/2003 LISA LESNY OUT TO CUSTOMER Completed