Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: REVISION
Permit Number - T03CM05308
Review Name: REVISION
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/22/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T03CM05308 DENIED 4/22/04 1. Registrant shall make revision to sealed drawings, which shall be submitted as full size. 2. #6 GND between the gutter and fused disconnects shall be #4. Per NEC Table 250-66, 3/0 phase conductors require #4. |