Review Date Reviewer's Name Type of Review Description Status Comments
04/22/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T03CM05308 DENIED 4/22/04
1. Registrant shall make revision to sealed drawings, which shall be submitted as full size.
2. #6 GND between the gutter and fused disconnects shall be #4. Per NEC Table 250-66, 3/0 phase conductors require #4.