Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T03CM05308
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/05/2004 | Robert Sherry | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 02/05/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 02/10/2004 | Martin Haeberle | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/11/2004 | Linda Buczynski | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/26/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
| 02/20/2004 | ANGIE SHOFFSTALL | APPROVAL SHELF | Completed |