Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T03CM05290
Parcel: 12613018A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM05290
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/06/2003 JIM EGAN FIRE REVIEW Approved
11/06/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
11/06/2003 MICHAEL ST. PAUL ZONING REVIEW Approved
11/06/2003 ROBERT SHERRY WATER REVIEW Approved
11/06/2003 LOREN MAKUS ENGINEERING REVIEW Approved
11/06/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide auxilliary or secondary drain for the fan coil unit. Reference section 307.2.3, IMC 2000.
11/12/2003 DROBEY1 BUILDING-COMMERCIAL REVIEW Needs Review
11/12/2003 DROBEY1 WWM REVIEW Passed
11/12/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T03CM05290 DENIED 11/7/03
1. Equipment Grounding Conductors in Panel Feeders are undersized at #8. Provide minimum of #1 per NEC 250-122 ( a).
2. Panelboard C appears to be powering AH-2 or AH-3, not AH-1, from the load calc. Please clarify.
3. Provide maintenance receptacles for the Air Handlers per NEC 210-63.
4. Specify which Conditioning Unit is used, CU-1, CU-2, or Cu-3.