Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/06/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
11/06/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
11/06/2003 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
11/06/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
11/06/2003 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
11/06/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide auxilliary or secondary drain for the fan coil unit. Reference section 307.2.3, IMC 2000. |
11/12/2003 | DROBEY1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
11/12/2003 | DROBEY1 | WWM | REVIEW | Passed | |
11/12/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T03CM05290 DENIED 11/7/03 1. Equipment Grounding Conductors in Panel Feeders are undersized at #8. Provide minimum of #1 per NEC 250-122 ( a). 2. Panelboard C appears to be powering AH-2 or AH-3, not AH-1, from the load calc. Please clarify. 3. Provide maintenance receptacles for the Air Handlers per NEC 210-63. 4. Specify which Conditioning Unit is used, CU-1, CU-2, or Cu-3. |