Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T03CM05290
Parcel: 12613018A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM05290
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/06/2003 JIM EGAN FIRE REVIEW Approved
11/06/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
11/06/2003 MICHAEL ST. PAUL ZONING REVIEW Approved
11/06/2003 ROBERT SHERRY WATER REVIEW Approved
11/06/2003 LOREN MAKUS ENGINEERING REVIEW Approved
11/06/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide auxilliary or secondary drain for the fan coil unit. Reference section 307.2.3, IMC 2000.
11/12/2003 DROBEY1 BUILDING-COMMERCIAL REVIEW Needs Review
11/12/2003 DROBEY1 WWM REVIEW Passed
11/12/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T03CM05290 DENIED 11/7/03
1. Equipment Grounding Conductors in Panel Feeders are undersized at #8. Provide minimum of #1 per NEC 250-122 ( a).
2. Panelboard C appears to be powering AH-2 or AH-3, not AH-1, from the load calc. Please clarify.
3. Provide maintenance receptacles for the Air Handlers per NEC 210-63.
4. Specify which Conditioning Unit is used, CU-1, CU-2, or Cu-3.